KNX devices that use KNX Connection Authorization and support Option 1 are, depending on the implementation, vulnerable to being locked and users being unable to reset them to gain access to the device. The BCU key feature on the devices can be used to create a password for the device, but this password can often not be reset without entering the current password. If the device is configured to interface with a network, an attacker with access to that network could interface with the KNX installation, purge all devices without additional security options enabled, and set a BCU key, locking the device. Even if a device is not connected to a network, an attacker with physical access to the device could also exploit this vulnerability in the same way.
See how the publisher's advisory changed over time. Each link opens the version saved at that time. The publisher's update date can differ from the date shown here.
How advisory history works
Each link identifies one complete publisher record. History can include advisories that previously shared an identifier; an identifier removed by a publisher no longer establishes a current relationship. A historical link shows only that record and earlier saved versions. Failed checks and unchanged reads do not create new versions.
KNX devices that use KNX Connection Authorization and support Option 1 are, depending on the implementation, vulnerable to being locked and users being unable to reset them to gain access to the device. The BCU key feature on the devices ca…