Inductive Automation Ignition Execution with Unnecessary Privileges
cve-program · CVE-2025-13911 · Published
No access to your tenant or devices. Every item links to its source. What this means
Historical advisory recorded 23 Oct 2026 15:48:27 UTC. Read the latest advisory.
Ignition by Inductive Automation, when installed with default OS service account settings, may expose the host system to an elevated code execution risk via the gateway backup restore functionality. An authenticated user with Gateway Administrator privileges can import a malicious gateway backup (.gwbk) file containing crafted project resources, scripts, or modules, resulting in code execution on the host system. This affects both Windows and Linux installations. On Windows, default installations often run the Ignition service as NT AUTHORITY\SYSTEM, resulting in code execution with full local system privileges. On Linux, default installations commonly run the Ignition service as root or with elevated privileges. Specific privilege level depends on installation configuration.
Read the publisher's advisorySee how the publisher's advisory changed over time. Each link opens the version saved at that time. The publisher's update date can differ from the date shown here.
Each link identifies one complete publisher record. History can include advisories that previously shared an identifier; an identifier removed by a publisher no longer establishes a current relationship. A historical link shows only that record and earlier saved versions. Failed checks and unchanged reads do not create new versions.
cve-program · CVE-2025-13911 · Published
This historical link shows only this version and versions saved before it. Browse all advisory history.