Red Lion Controls N-Tron 700 Series Insufficiently Protected Credentials
Exact source revision recorded 23 Oct 2026 15:48:27 UTC. It does not establish the source's current position. Latest evidence.
cve-program · CVE-2026-39460
PublishedUsernames and passwords, including the default factory credentials, are stored in plaintext within the configuration file. With administrator rights, the configuration file can be viewed through the CLI or they can be exported from the device through a TFTP transfer from the web interface. A TFTP transfer can be initiated through SNMP which does not require authentication.
- Source published
- 9 Oct 2026 14:30:47 UTC
- Source modified
- 12 Oct 2026 22:54:01 UTC
- Observed here
- 23 Oct 2026 15:48:27 UTC
- Source terms
- CVE Program Terms of Use
Original source record · Cite this exact observation · Complete original publisher JSON
This view projects the publisher's source fields for reading; the original JSON retains additional fields and CVE enrichment containers. Attribution: cve-program · CVE Program Terms of Use. Source text is retained; field grouping and change labels are provided by ChangeIntel.
CVSS 3.1 · 8.1 CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:N
CVSS 4.0 · 9.3 CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:N/SC:H/SI:H/SA:N