Inductive Automation Ignition Incorrect Default Permissions
Historical advisory recorded 23 Oct 2026 15:48:27 UTC. Read the latest advisory.
cve-program · CVE-2026-77393
PublishedIn Ignition 8.1.53 and earlier, the Gateway "Create Project Role(s)" setting shipped blank, which permitted any authenticated user to create projects (if they can execute gateway scripts). Ignition 8.1.54 restricts project creation to Designer sessions and no longer relies on this setting. The 8.3 series is not affected.
Read the publisher's advisoryAffected versions, risk and source history
cve-program · CVE-2026-77393
PublishedInductive Automation Ignition Incorrect Default Permissions
In Ignition 8.1.53 and earlier, the Gateway "Create Project Role(s)" setting shipped blank, which permitted any authenticated user to create projects (if they can execute gateway scripts). Ignition 8.1.54 restricts project creation to Designer sessions and no longer relies on this setting. The 8.3 series is not affected.
- Source published
- 4 Sep 2026 21:10:25 UTC
- Source modified
- 7 Sep 2026 11:17:27 UTC
- Saved here
- 23 Oct 2026 15:48:27 UTC
- Source terms
- CVE Program Terms of Use
Original source record · Cite this exact observation · Complete original publisher JSON
Source: cve-program · CVE Program Terms of Use. The publisher's wording is preserved. ChangeIntel groups the information and labels changes. The JSON record includes additional source fields.
CVSS 3.1 · 8.8 CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H
CVSS 4.0 · 8.7 CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N